Heat Exchanger Design Skill
Purpose
The Heat Exchanger Design skill provides comprehensive capabilities for sizing, rating, and optimizing heat exchangers according to TEMA standards, enabling systematic thermal-hydraulic design of shell-and-tube, plate, and air-cooled heat exchanger configurations.
Capabilities
- Shell-and-tube heat exchanger design and rating
- Plate heat exchanger sizing
- Air-cooled heat exchanger configuration
- LMTD and effectiveness-NTU methods
- Fouling factor consideration
- Pressure drop calculations
- HTRI Xchanger Suite integration
- Thermal-hydraulic optimization
Usage Guidelines
Design Methods
LMTD Method
Log Mean Temperature Difference
LMTD = (ΔT1 - ΔT2) / ln(ΔT1/ΔT2)
Q = U × A × F × LMTD
Where:
F = Correction factor for non-counterflow
U = Overall heat transfer coefficient
A = Heat transfer area
LMTD Correction Factors
- One shell pass, 2/4/6 tube passes
- Two shell passes, 4/8 tube passes
- Crossflow configurations
Effectiveness-NTU Method
Effectiveness Definition
ε = Q_actual / Q_max
Q_max = Cmin × (Th,in - Tc,in)
NTU Calculation
NTU = UA / Cmin
Cr = Cmin / Cmax
Effectiveness Relations
- Counterflow: ε = (1-exp(-NTU(1-Cr)))/(1-Cr×exp(-NTU(1-Cr)))
- Parallel flow: ε = (1-exp(-NTU(1+Cr)))/(1+Cr)
- Shell-and-tube: Complex correlations by TEMA type
Shell-and-Tube Design
TEMA Designations
| Front End |
Shell |
Rear End |
| A - Channel |
E - One-pass |
L - Fixed tubesheet |
| B - Bonnet |
F - Two-pass |
M - Fixed tubesheet |
| N - Channel |
J - Divided flow |
N - Fixed tubesheet |
| - |
X - Crossflow |
P - Outside packed |
| - |
- |
S - Floating head |
| - |
- |
U - U-tube |
Tube Layout
- Triangular pitch (30°): Maximum tubes, poor cleaning
- Square pitch (90°): Mechanical cleaning possible
- Rotated square (45°): Higher turbulence
Baffle Design
- Segmental: 20-45% cut
- Double segmental: Reduced pressure drop
- No-tubes-in-window: Vibration mitigation
Plate Heat Exchanger
Plate Selection
- Chevron angle (25-65°): Trade-off h vs ΔP
- Plate spacing: 2-5 mm typical
- Pass arrangement: U or Z configuration
Design Considerations
- Maximum pressure: 25-30 bar typical
- Maximum temperature: 150-200°C (gaskets)
- Fouling service: Not ideal
Air-Cooled Heat Exchanger
Configuration
- Forced draft: Fan below bundle
- Induced draft: Fan above bundle
- Natural draft: No fan (limited duty)
Design Parameters
- Face velocity: 2.5-3.5 m/s
- Tube rows: 3-6 typical
- Fin density: 275-435 fins/m
Fouling Considerations
| Service |
Fouling Factor (m²K/kW) |
| Cooling water |
0.2-0.35 |
| River water |
0.35-0.5 |
| Fuel oil |
0.5-0.9 |
| Heavy hydrocarbons |
0.35-0.7 |
| Light hydrocarbons |
0.1-0.2 |
| Steam (clean) |
0.05-0.1 |
Process Integration
- ME-012: Heat Exchanger Design and Rating
- ME-011: Thermal Management Design
Input Schema
{
"design_type": "sizing|rating",
"exchanger_type": "shell_tube|plate|air_cooled",
"hot_fluid": {
"name": "string",
"flow_rate": "number (kg/s)",
"inlet_temp": "number (C)",
"outlet_temp": "number (C, for sizing)"
},
"cold_fluid": {
"name": "string",
"flow_rate": "number (kg/s)",
"inlet_temp": "number (C)",
"outlet_temp": "number (C, for sizing)"
},
"pressure_constraints": {
"hot_side_max_dp": "number (kPa)",
"cold_side_max_dp": "number (kPa)"
},
"fouling_factors": {
"hot_side": "number (m2K/kW)",
"cold_side": "number (m2K/kW)"
}
}
Output Schema
{
"duty": "number (kW)",
"geometry": {
"type": "string (TEMA designation or plate type)",
"area": "number (m2)",
"shell_diameter": "number (mm)",
"tube_count": "number",
"tube_length": "number (m)"
},
"thermal": {
"LMTD": "number (C)",
"F_factor": "number",
"U_clean": "number (W/m2K)",
"U_dirty": "number (W/m2K)"
},
"hydraulic": {
"shell_side_dp": "number (kPa)",
"tube_side_dp": "number (kPa)"
},
"performance": {
"effectiveness": "number",
"NTU": "number"
}
}
Best Practices
- Always include fouling factors appropriate for the service
- Verify pressure drop constraints are met on both sides
- Check for vibration potential in shell-and-tube designs
- Consider maintenance access in configuration selection
- Apply TEMA tolerances for manufacturing variations
- Use conservative correlations for preliminary sizing
Integration Points
- Connects with CFD Analysis for detailed flow distribution
- Feeds into HVAC System Design for system integration
- Supports Thermal Analysis for component-level design
- Integrates with Process Design for plant-level optimization
1---
2name: heat-exchanger-design
3description: Specialized skill for heat exchanger sizing, rating, and optimization per TEMA standards including shell-and-tube, plate, and air-cooled configurations
4allowed-tools:
5 - Read
6 - Write
7 - Glob
8 - Grep
9 - Bash
10metadata:
11 source: https://skillmd.com/skills/a5c-ai/heat-exchanger-design
12 specialization: mechanical-engineering
13 domain: science
14 category: thermal-fluid-analysis
15 priority: high
16 phase: 6
17 tools-libraries:
18 - HTRI Xchanger Suite
19 - Aspen Exchanger Design and Rating
20graph:
21 domains: [domain:mechanical-engineering]
22 skillAreas: [skill-area:physics-simulation, skill-area:mathematical-reasoning, skill-area:motion-planning]
23 roles: [role:systems-integration-engineer, role:research-engineer]
24---
25
26# Heat Exchanger Design Skill
27
28## Purpose
29
30The Heat Exchanger Design skill provides comprehensive capabilities for sizing, rating, and optimizing heat exchangers according to TEMA standards, enabling systematic thermal-hydraulic design of shell-and-tube, plate, and air-cooled heat exchanger configurations.
31
32## Capabilities
33
34- Shell-and-tube heat exchanger design and rating
35- Plate heat exchanger sizing
36- Air-cooled heat exchanger configuration
37- LMTD and effectiveness-NTU methods
38- Fouling factor consideration
39- Pressure drop calculations
40- HTRI Xchanger Suite integration
41- Thermal-hydraulic optimization
42
43## Usage Guidelines
44
45### Design Methods
46
47#### LMTD Method
48
491. **Log Mean Temperature Difference**
50 ```
51 LMTD = (ΔT1 - ΔT2) / ln(ΔT1/ΔT2)
52
53 Q = U × A × F × LMTD
54
55 Where:
56 F = Correction factor for non-counterflow
57 U = Overall heat transfer coefficient
58 A = Heat transfer area
59 ```
60
612. **LMTD Correction Factors**
62 - One shell pass, 2/4/6 tube passes
63 - Two shell passes, 4/8 tube passes
64 - Crossflow configurations
65
66#### Effectiveness-NTU Method
67
681. **Effectiveness Definition**
69 ```
70 ε = Q_actual / Q_max
71 Q_max = Cmin × (Th,in - Tc,in)
72 ```
73
742. **NTU Calculation**
75 ```
76 NTU = UA / Cmin
77 Cr = Cmin / Cmax
78 ```
79
803. **Effectiveness Relations**
81 - Counterflow: ε = (1-exp(-NTU(1-Cr)))/(1-Cr×exp(-NTU(1-Cr)))
82 - Parallel flow: ε = (1-exp(-NTU(1+Cr)))/(1+Cr)
83 - Shell-and-tube: Complex correlations by TEMA type
84
85### Shell-and-Tube Design
86
871. **TEMA Designations**
88 | Front End | Shell | Rear End |
89 |-----------|-------|----------|
90 | A - Channel | E - One-pass | L - Fixed tubesheet |
91 | B - Bonnet | F - Two-pass | M - Fixed tubesheet |
92 | N - Channel | J - Divided flow | N - Fixed tubesheet |
93 | - | X - Crossflow | P - Outside packed |
94 | - | - | S - Floating head |
95 | - | - | U - U-tube |
96
972. **Tube Layout**
98 - Triangular pitch (30°): Maximum tubes, poor cleaning
99 - Square pitch (90°): Mechanical cleaning possible
100 - Rotated square (45°): Higher turbulence
101
1023. **Baffle Design**
103 - Segmental: 20-45% cut
104 - Double segmental: Reduced pressure drop
105 - No-tubes-in-window: Vibration mitigation
106
107### Plate Heat Exchanger
108
1091. **Plate Selection**
110 - Chevron angle (25-65°): Trade-off h vs ΔP
111 - Plate spacing: 2-5 mm typical
112 - Pass arrangement: U or Z configuration
113
1142. **Design Considerations**
115 - Maximum pressure: 25-30 bar typical
116 - Maximum temperature: 150-200°C (gaskets)
117 - Fouling service: Not ideal
118
119### Air-Cooled Heat Exchanger
120
1211. **Configuration**
122 - Forced draft: Fan below bundle
123 - Induced draft: Fan above bundle
124 - Natural draft: No fan (limited duty)
125
1262. **Design Parameters**
127 - Face velocity: 2.5-3.5 m/s
128 - Tube rows: 3-6 typical
129 - Fin density: 275-435 fins/m
130
131### Fouling Considerations
132
133| Service | Fouling Factor (m²K/kW) |
134|---------|------------------------|
135| Cooling water | 0.2-0.35 |
136| River water | 0.35-0.5 |
137| Fuel oil | 0.5-0.9 |
138| Heavy hydrocarbons | 0.35-0.7 |
139| Light hydrocarbons | 0.1-0.2 |
140| Steam (clean) | 0.05-0.1 |
141
142## Process Integration
143
144- ME-012: Heat Exchanger Design and Rating
145- ME-011: Thermal Management Design
146
147## Input Schema
148
149```json
150{
151 "design_type": "sizing|rating",
152 "exchanger_type": "shell_tube|plate|air_cooled",
153 "hot_fluid": {
154 "name": "string",
155 "flow_rate": "number (kg/s)",
156 "inlet_temp": "number (C)",
157 "outlet_temp": "number (C, for sizing)"
158 },
159 "cold_fluid": {
160 "name": "string",
161 "flow_rate": "number (kg/s)",
162 "inlet_temp": "number (C)",
163 "outlet_temp": "number (C, for sizing)"
164 },
165 "pressure_constraints": {
166 "hot_side_max_dp": "number (kPa)",
167 "cold_side_max_dp": "number (kPa)"
168 },
169 "fouling_factors": {
170 "hot_side": "number (m2K/kW)",
171 "cold_side": "number (m2K/kW)"
172 }
173}
174```
175
176## Output Schema
177
178```json
179{
180 "duty": "number (kW)",
181 "geometry": {
182 "type": "string (TEMA designation or plate type)",
183 "area": "number (m2)",
184 "shell_diameter": "number (mm)",
185 "tube_count": "number",
186 "tube_length": "number (m)"
187 },
188 "thermal": {
189 "LMTD": "number (C)",
190 "F_factor": "number",
191 "U_clean": "number (W/m2K)",
192 "U_dirty": "number (W/m2K)"
193 },
194 "hydraulic": {
195 "shell_side_dp": "number (kPa)",
196 "tube_side_dp": "number (kPa)"
197 },
198 "performance": {
199 "effectiveness": "number",
200 "NTU": "number"
201 }
202}
203```
204
205## Best Practices
206
2071. Always include fouling factors appropriate for the service
2082. Verify pressure drop constraints are met on both sides
2093. Check for vibration potential in shell-and-tube designs
2104. Consider maintenance access in configuration selection
2115. Apply TEMA tolerances for manufacturing variations
2126. Use conservative correlations for preliminary sizing
213
214## Integration Points
215
216- Connects with CFD Analysis for detailed flow distribution
217- Feeds into HVAC System Design for system integration
218- Supports Thermal Analysis for component-level design
219- Integrates with Process Design for plant-level optimization