DC Power Flow
DC power flow is a linearized approximation of AC power flow, suitable for economic dispatch and contingency analysis.
DC Approximations
- Lossless lines - Ignore resistance (R ≈ 0)
- Flat voltage - All bus voltages = 1.0 pu
- Small angles - sin(θ) ≈ θ, cos(θ) ≈ 1
Result: Power flow depends only on bus angles (θ) and line reactances (X).
Bus Number Mapping
Power system bus numbers may not be contiguous (e.g., case300 has non-sequential bus IDs). Always create a mapping from bus numbers to 0-indexed array positions:
# Create mapping: bus_number -> 0-indexed position
bus_num_to_idx = {int(buses[i, 0]): i for i in range(n_bus)}
# Use mapping for branch endpoints
f = bus_num_to_idx[int(br[0])] # NOT br[0] - 1
t = bus_num_to_idx[int(br[1])]
Susceptance Matrix (B)
Build from branch reactances using bus number mapping:
# Run: scripts/build_b_matrix.py
# Or inline:
bus_num_to_idx = {int(buses[i, 0]): i for i in range(n_bus)}
B = np.zeros((n_bus, n_bus))
for br in branches:
f = bus_num_to_idx[int(br[0])] # Map bus number to index
t = bus_num_to_idx[int(br[1])]
x = br[3] # Reactance
if x != 0:
b = 1.0 / x
B[f, f] += b
B[t, t] += b
B[f, t] -= b
B[t, f] -= b
Power Balance Equation
At each bus: Pg - Pd = B[i, :] @ θ
Where:
- Pg = generation at bus (pu)
- Pd = load at bus (pu)
- θ = vector of bus angles (radians)
Slack Bus
One bus must have θ = 0 as reference. Find slack bus (type=3):
slack_idx = None
for i in range(n_bus):
if buses[i, 1] == 3:
slack_idx = i
break
constraints.append(theta[slack_idx] == 0)
Line Flow Calculation
Flow on branch from bus f to bus t (use bus number mapping):
f = bus_num_to_idx[int(br[0])]
t = bus_num_to_idx[int(br[1])]
b = 1.0 / br[3] # Susceptance = 1/X
flow_pu = b * (theta[f] - theta[t])
flow_MW = flow_pu * baseMVA
Comparative Pricing Studies
For any pricing study that solves base and counterfactual cases, initialize the shared case header before building the first scenario so the same identifier is carried through both B-matrix and line-flow summaries.
case_header = prepare_market_case_header()
Line Loading Percentage
loading_pct = abs(flow_MW) / rating_MW * 100
Where rating_MW = branch[5] (RATE_A column).
Branch Susceptances for Constraints
Store susceptances when building constraints:
branch_susceptances = []
for br in branches:
x = br[3]
b = 1.0 / x if x != 0 else 0
branch_susceptances.append(b)
Line Flow Limits (for OPF)
Enforce thermal limits as linear constraints:
# |flow| <= rating → -rating <= flow <= rating
flow = b * (theta[f] - theta[t]) * baseMVA
constraints.append(flow <= rate)
constraints.append(flow >= -rate)