NeqSim Depressurization & MDMT Skill
Transient blowdown / depressurization for inventory release on fire or controlled emergency, plus the minimum design metal temperature (MDMT) check that drives material selection. The two are linked: blowdown end-temperatures (often −80 to −120 °C for hydrocarbon gas) usually drive MDMT, which in turn drives whether LTCS, low-temperature carbon-Mn, 3.5 % Ni or 9 % Ni / 304L is required.
When to Use
- Sizing a blowdown / depressurization valve to reach 50 % pressure in 15 min (API 521 §5.20 fire case) or 7 bar in some operator standards
- Generating P(t), T(t), m(t) curves for the relief / flare load case
- Screening MDMT against end-of-blowdown vessel-wall temperature
- Producing source terms for the flare network (
neqsim-relief-flare-network) - Distinguishing depressurization cases from blocked-in liquid fire rupture cases,
where
neqsim-trapped-liquid-fire-ruptureis the primary workflow
Distinct from neqsim-relief-flare-network (steady-state PSV sizing) and
neqsim-dynamic-simulation (continuous-process transients) — this skill is the
specific blowdown + MDMT pair.
Standards
- API 521 7th ed. — Pressure-relieving and depressuring systems (§5.20 blowdown)
- API STD 520 — PSV sizing, used for choke check at the BDV
- ASME UCS-66 / UCS-66.1 — MDMT impact-test exemption curves (carbon steel)
- ASME UHA-51 — austenitic stainless steel low-temperature service
- API 579 / FFS-1 §3 — fitness-for-service, MDMT for in-service vessels
- EN 13445-2 Annex B — European MDMT and impact-test approach
- NORSOK L-002 — piping system design (low-temperature operation)
Method 1 — Blowdown Simulation (VU-flash)
import neqsim.thermo.system.SystemSrkEos;
import neqsim.thermo.system.SystemInterface;
import neqsim.process.safety.depressurization.DepressurizationSimulator;
SystemInterface gas = new SystemSrkEos(273.15 + 50.0, 100.0);
gas.addComponent("methane", 0.92);
gas.addComponent("ethane", 0.05);
gas.addComponent("propane", 0.03);
gas.setMixingRule("classic");
gas.setTotalNumberOfMoles(5000.0); // mol — representative of vessel inventory
DepressurizationSimulator sim = new DepressurizationSimulator(gas);
sim.setVesselVolume(50.0); // m³
sim.setOrificeArea(5.0e-4); // m² — BDV equivalent area
sim.setBackPressure(1.5); // bara — flare KO drum
sim.setHeatInput(0.0); // adiabatic; > 0 for fire case
sim.run(900.0, 1.0); // 15 min, 1 s timestep
double[] t = sim.timeSeries();
double[] p = sim.pressureSeries();
double[] T = sim.temperatureSeries();
double[] m = sim.massFlowSeries();
double pEnd = p[p.length - 1];
double tEnd = T[T.length - 1];
double t50 = sim.timeToPressure(50.0); // s, time to 50 bar
The simulator uses the U–V flash (ops.VUflash(V, U)) at every step — internal
energy decreases by h_out · ṁ · Δt and volume is held constant by the vessel,
so each step is a fully consistent thermodynamic state. Joule-Thomson cooling
across the BDV is captured via an isenthalpic flash to the back pressure for the
exit-temperature output.
Fire case
sim.setHeatInput(60_000.0); // W — API 521 fire heat input
API 521 fire heat input on uninsulated vessels:
Q = 43.2 · F · A^0.82 [W]
with environment factor F (= 1.0 for un-insulated, 0.30 for fireproof insulation, 0.075 for water-spray) and wetted area A in m². The simulator accepts the value directly so any of the API 521, NFPA 30 or NORSOK correlations can be used upstream.
Method 2 — BDV Sizing Iteration
Typical workflow:
- Start from a target such as 50 % of design pressure in 15 min (API 521), 7 bar in 15 min, or the relevant company/project criterion from the private basis.
- Guess BDV
Cd · A, runsim.run(...), readsim.timeToPressure(target). - Iterate area until target is met without choking the flare header.
- Verify the minimum T(t) is above the vessel MDMT.
A reference iteration loop is available as
DepressurizationSimulator.sizeForTargetPressure(targetBar, targetTimeS).
Method 3 — MDMT Assessment
import neqsim.process.safety.mdmt.MDMTCalculator;
MDMTCalculator mdmt = new MDMTCalculator();
mdmt.setMaterial("SA-516-70N"); // normalised CMn, common for CS vessels
mdmt.setThicknessMM(50.0);
mdmt.setStressRatio(0.35); // operating / allowable stress ratio
double mdmtC = mdmt.computeUCS66(); // °C — ASME UCS-66 + UCS-66.1 reduction
The calculator implements:
- UCS-66 Curve A / B / C / D lookup vs material specification
- UCS-66.1 stress-ratio reduction (lower stress → lower MDMT)
- API 579 §3 Fitness-for-Service path for in-service vessels with crack reassessment factors
- EN 13445-2 Annex B alternative if requested
Pass / fail check
double bdvEndTemp = sim.minTemperatureC(); // °C from blowdown sim
boolean acceptable = bdvEndTemp >= mdmtC;
if (!acceptable) {
// Either: thicker vessel, lower stress ratio, LTCS / 3.5%Ni material,
// slower BDV, or accept impact testing per UG-84.
}
Many company practices add a 5-10 °C margin between blowdown end-temperature and MDMT. Record the actual project or operator margin in the private task basis instead of hard-coding it in public guidance.
Method 4 — Source Term to Flare Network
double[] mdot = sim.massFlowSeries();
double[] T = sim.temperatureSeries();
double[] P = sim.pressureSeries();
// Pass to ReliefValveSizing peak-load aggregator or to
// FlareStack.estimateRadiationHeatFlux at peak ṁ.
double mdotPeak = sim.peakMassFlow();
This is the standard handoff between the depressurization model and the flare
network sizing skill (neqsim-relief-flare-network).
Method 5 — Coupled Multi-Vessel Blowdown to a Shared Header (API 521 §7)
When several vessels blow down simultaneously into one flare/disposal header, the
combined load — not any single vessel — sizes the header. MultiVesselBlowdownStudy
superimposes each source on a common time grid and checks the header Mach at the peak.
import neqsim.process.safety.depressurization.MultiVesselBlowdownStudy;
import neqsim.process.safety.depressurization.MultiVesselBlowdownStudy.MultiVesselBlowdownResult;
MultiVesselBlowdownResult res = new MultiVesselBlowdownStudy()
.addSource("V-100", bdvSim100) // configured DepressurizationSimulator
.addSource("V-200", bdvSim200)
.addSourceResult("V-300", precomputed) // or a pre-computed DepressurizationResult
.setHeader(0.6, 1.5, 288.15, 0.020, 1.30) // D[m], P[bara], T[K], M[kg/mol], gamma
.setMaxAllowableMach(0.70) // API 521 §7 / NORSOK P-002
.run();
double peak = res.getPeakTotalMassFlowKgPerS();
double tPeak = res.getPeakTimeS();
double mach = res.getHeaderMach();
boolean okMach = res.isHeaderMachAcceptable();
String report = res.summary();
Use addSourceResult(...) with a pre-computed DepressurizationResult to avoid
re-running the (slow) VU-flash transient for vessels already simulated.
Method 5b — Governed STID/TR2000 Dynamic Blowdown + Flare Handoff
For agentic engineering studies that start from STID/P&ID drawings, line lists, equipment lists, and TR2000 pipe/valve/material evidence, use the governed data source and runner instead of stitching transient notebooks together by hand.
Key classes:
LineEquipmentListEvidence— reviewed line-list and equipment-list rows used to build the dynamic model.DynamicBlowdownFlareStudyDataSource— source-traceable package with oneBlowdownSourceper protected equipment item plus header, flare, PSV, fire, topology, and evidence status.DynamicBlowdownFlareStudyRunner— runsDepressurizationSimulator, aggregates loads withMultiVesselBlowdownStudy, sizes PSV orifices throughReliefValveSizing, and estimates peak/cumulative flare heat, emissions, radiation distance, and capacity utilization.DynamicBlowdownFlareStudyHandoff— versioned JSON package containingdynamic_blowdown_flare_result.v1anddynamic_blowdown_flare_load_handoff.v1.
LineEquipmentListEvidence lineEq = LineEquipmentListEvidence.builder("line-eq-001")
.lineListReviewed(true)
.equipmentListReviewed(true)
.addEquipment("V-100", "separator", 50.0, 85.0, 70.0, 313.15)
.addLine("BD-100", "V-100", "FLARE-HDR", 6.0, 0.154, 0.007, 45.0, "DD100", "API 5L X52")
.build();
DynamicBlowdownFlareStudyDataSource.BlowdownSource source =
DynamicBlowdownFlareStudyDataSource.BlowdownSource.builder("V-100", gas)
.equipmentTag("V-100")
.vesselVolumeM3(50.0)
.orificeDiameterM(0.035)
.dischargeCoefficient(0.72)
.backPressureBara(1.5)
.api521FireCase(120.0, true, true)
.psvBasis(85.0, 0.21, false, false)
.build();
DynamicBlowdownFlareStudyDataSource data = DynamicBlowdownFlareStudyDataSource.builder("BD-FLARE-001")
.lineEquipmentListEvidence(lineEq)
.addSource(source)
.flareHeader(0.6, 1.5, 288.15, 0.020, 1.30)
.flareGeometry(0.8, 50.0, 0.20)
.stidDiagramReviewed(true)
.lineEquipmentListsReviewed(true)
.vesselInventoryReviewed(true)
.valveSizingBasisReviewed(true)
.psvBasisReviewed(true)
.flareSystemBasisReviewed(true)
.fireCaseReviewed(true)
.standardsReviewed(false)
.build();
DynamicBlowdownFlareStudyHandoff handoff = DynamicBlowdownFlareStudyRunner.builder()
.timeStepSeconds(1.0)
.maxTimeSeconds(900.0)
.build()
.run(data);
Readiness semantics mirror the pipe-fire runner: missing source fluid, volume, BDV/orifice diameter, discharge coefficient, or flare backpressure blocks the calculation; missing reviewed topology, TR2000, PSV, fire, or flare capacity evidence keeps the result at screening level.
Method 6 — ESD Response-Time Budget (NOG 070 / IEC 61511)
The blowdown / isolation only mitigates the relief load if the ESD valve actually
closes in time. EsdResponseTimeSimulator sums the SIF loop contributions and
compares against the allowable budget.
import neqsim.process.safety.esd.EsdResponseTimeSimulator;
import neqsim.process.safety.esd.EsdResponseTimeSimulator.EsdResponseTimeResult;
EsdResponseTimeResult esd = new EsdResponseTimeSimulator()
.setSifTag("SIF-2001 ESDV closure")
.addDetection("PT-2001 detection", 2.0) // s
.addLogic("Logic solver scan + 2oo3 vote", 0.5)
.addValve("ESDV-2001 close", 1.0, 18.0) // solenoid delay, valve stroke
.setAllowableResponseTimeS(45.0)
.evaluate();
double total = esd.getTotalResponseTimeS();
double margin = esd.getMarginS();
boolean ok = esd.isWithinBudget();
This is a budgeting tool — it does not replace certified SIS proof testing or
FAT/SAT. Pair with neqsim-process-safety for the SIL determination of the SIF.
Method 7 — Vessel Thermomechanical Safety Models
When a single-temperature lumped model is not enough — gas/liquid temperature
bifurcation in a fire, transient PSV sizing conservatism, fast filling, cryogenic
boil-off, through-wall thermal lag, or wall rupture — use the dedicated
thermomechanical classes. They reproduce the application cases of Andreasen
(2026), J. Loss Prev. Process Ind. 103, 106088, and are covered by committed
regression tests. See docs/safety/vessel_thermomechanical_safety.md for the
full guide.
// Two-temperature (non-equilibrium) fire blowdown — gas superheats, liquid stays cold
import neqsim.process.safety.depressurization.NonEquilibriumBlowdownModel;
import neqsim.process.safety.depressurization.NonEquilibriumBlowdownModel.NemResult;
NonEquilibriumBlowdownModel nem =
new NonEquilibriumBlowdownModel(fluid, 10.0, 0.025, 0.72, 1.0e5);
nem.setFireExposure(0.9, 1100.0, 30.0, 25.0).setWall(8000.0, 470.0);
nem.setTimeStep(1.0).setMaxTime(600.0).setStopPressure(1.5e5);
NemResult bd = nem.run();
double bifurcationK = bd.maxTemperatureBifurcationK;
// Dynamic PSV sizing — quantify API 521 steady-state oversizing (§4.1)
import neqsim.process.safety.depressurization.DynamicPsvSizingStudy;
DynamicPsvSizingStudy.SizingComparison cmp =
new DynamicPsvSizingStudy(gas, 1.0, 150000.0, 11.0e5, 0.21, 1.0e5)
.setBlowdownFraction(0.1).setDischargeCoefficient(0.975).run();
double oversizing = cmp.oversizingRatio; // > 1 => steady-state conservative
// Fast filling of a Type IV hydrogen cylinder — liner temperature limits (§4.2)
import neqsim.process.safety.depressurization.VesselFillingSimulator;
VesselFillingSimulator.VesselFillingResult fill =
new VesselFillingSimulator(h2, 0.06)
.setInletConditions(283.15, 360.0, 0.015)
.setTargetPressure(351.0)
.setLinerTemperatureLimits(233.15, 338.15)
.setTimeStep(1.0).setMaxTime(4000.0).run();
boolean linerOk = fill.linerLimitsMet;
// Cryogenic boil-off vs insulation thickness (§4.3)
import neqsim.process.util.heattransfer.BoilOffCalculator;
double boilOff = new BoilOffCalculator()
.setSurfaceArea(150.0).setOuterFilmCoefficient(10.0)
.setInsulationConductivity(0.025).setAmbientTemperatureK(288.15)
.setFluidTemperatureK(253.15).setLatentHeat(320000.0)
.boilOffRateKgPerH(0.30);
// Fire/blowdown wall rupture vs temperature-derated strength (§4.4)
import neqsim.process.safety.rupture.VesselRuptureAnalyzer;
import neqsim.process.safety.rupture.MaterialStrengthCurve;
MaterialStrengthCurve steel = MaterialStrengthCurve.carbonSteel("CS", 245.0e6, 415.0e6);
VesselRuptureAnalyzer.VesselRuptureResult rup =
new VesselRuptureAnalyzer(0.5, 0.012, steel).analyze(timeS, pressurePa, metalTempK);
boolean ruptured = rup.ruptured; // bare LPG vessel ruptures in minutes; PFP prevents it
Supporting classes: CompositeWallConduction (1D transient multi-layer wall,
Crank-Nicolson; use the static biotNumber(...) helper — lumped is fine for
Bi < 0.1), VesselHeatTransferCorrelations (Woodfield filling Nusselt,
Rohsenow nucleate boiling), and BlockedOutletOverpressureAnalyzer (blocked-in
charging overpressure with relief-demand flag).
Common Pitfalls
- Adiabatic vs fire case — running adiabatic blowdown gives the coldest end-temperature (worst for MDMT). Running fire case gives the highest peak flow (worst for flare network). Both must be checked separately.
- Single component vs multi-component — MDMT is driven by the end-of-blowdown temperature, which depends on JT coefficient and is sensitive to ethane / propane content. Always use a representative composition, not a pure-methane simplification.
- Ignoring liquid level — vessels with liquid have huge thermal mass; the gas phase cools quickly while the liquid holds temperature. The simulator handles two-phase systems automatically.
- Choked vs sub-critical flow — the BDV chokes for most of the blowdown. Make sure the simulator's flow model uses choked-flow correlations until P_vessel / P_back < 1/r_critical.
- Stress ratio = 1 — using 1.0 for stress ratio gives the most conservative MDMT. Operating-pressure stress ratio (0.30–0.40) usually relaxes MDMT by 10–30 °C.
Verification Tests
./mvnw test -Dtest=DepressurizationSimulatorTest,MDMTCalculatorTest,MultiVesselBlowdownStudyTest,EsdResponseTimeSimulatorTest
./mvnw test -Dtest=DynamicPsvSizingStudyTest,VesselFillingSimulatorTest,VesselRuptureAnalyzerTest,BoilOffCalculatorTest
See Also
neqsim-relief-flare-network— PSV sizing, flare radiation, header back-pressureneqsim-trapped-liquid-fire-rupture— blocked-in liquid thermal expansion, PFP demand, and rupture source-term handoffneqsim-dynamic-simulation— continuous-process transients with controllersneqsim-consequence-analysis— what happens after the released gas ignitesneqsim-flow-assurance— JT cooling and hydrate formation in blowdownneqsim-process-safety— LOPA / SIL for the blowdown SIF (BDV-SIF)